Vacuum relief valves are a critical safety component on vacuum tanks, vacuum trucks, and industrial vacuum systems. Their purpose is to protect the tank from excessive vacuum conditions that could damage equipment or cause catastrophic tank failure. Regular testing ensures the valve opens at the correct vacuum level and reseals properly after operation.
This guide outlines a simple and effective procedure for testing a 1.5" RIV Brass Vacuum Relief Valve, but the test method is essentially the same for any spring-loaded vacuum relief valve used on vacuum tanks.
Why Test a Vacuum Relief Valve?
A vacuum relief valve serves as the last line of defense against excessive vacuum buildup inside a tank. Over time, contamination, corrosion, spring fatigue, and normal wear can affect valve performance.
Routine testing helps verify that the valve:
- Opens at the proper vacuum setting
- Closes and seals correctly after activation
- Responds smoothly without sticking
- Protects the tank from over-vacuum conditions
Required Equipment
Before beginning the test, gather the following equipment:
- Vacuum pump capable of producing at least 20 inHg of vacuum
- Calibrated vacuum gauge
- Appropriate fittings and adapters for the valve connection
- Shop air source (optional for cleaning)
- Cleaning supplies and inspection tools
Step 1: Perform a Visual Inspection
Remove the valve from service and inspect it thoroughly.
Look for:
- Dirt or debris on the valve seat
- Corrosion inside the valve body
- Damaged sealing surfaces
- Broken or weakened springs
- Signs of product buildup
- Physical damage to the valve body
If contamination is present, clean the valve before testing.
Step 2: Connect the Test Setup
Install the valve onto a vacuum test fixture.
The setup should include:
- Vacuum source
- Calibrated vacuum gauge
- Test fittings
- Valve under test
Ensure all connections are airtight to prevent false readings.
Step 3: Apply Vacuum Slowly
Start the vacuum source and gradually increase vacuum.
Monitor the vacuum gauge while observing the valve.
As the vacuum approaches the valve's set point, the valve should begin to open and admit atmospheric air.
What to Watch For
- Smooth opening action
- No sticking or hesitation
- Consistent operation
- Audible airflow when the valve opens
Step 4: Record the Opening Point
When the valve first opens, note the vacuum reading on the gauge.
Compare this reading to the valve manufacturer's specified opening pressure.
If the valve:
- Opens below its rated setting, the spring may be weak or worn.
- Opens above its rated setting, contamination or internal binding may be preventing proper operation.
- Does not open at all, remove the valve from service immediately.
Step 5: Verify Proper Reseating
After the valve opens:
- Slowly reduce the vacuum level.
- Observe the valve as it closes.
- Verify the valve returns fully to the closed position.
The valve should:
- Close smoothly
- Seal completely
- Show no evidence of leakage
Step 6: Perform a Leak Test
Apply vacuum below the valve's opening point.
The valve should remain fully closed while maintaining vacuum.
Signs of leakage include:
- Loss of vacuum pressure
- Audible air leakage
- Inability to maintain a stable vacuum reading
Any leakage may indicate a damaged seat, worn seal, or contamination.

Field Testing on a Vacuum Tank
A basic functional test can also be performed with the valve installed on the tank.
Procedure
- Start the vacuum system.
- Monitor the tank vacuum gauge.
- Increase vacuum gradually.
- Observe the vacuum relief valve.
The valve should open at its designated setting and prevent the vacuum from increasing beyond the safe operating limit.
You may hear air being drawn through the valve when it activates.
Common Test Failures and Causes
| Symptom | Possible Cause |
|---|---|
| Opens too early | Weak spring, worn components |
| Opens too late | Dirt buildup, corrosion, sticking parts |
| Will not open | Seized mechanism, internal damage |
| Leaks continuously | Damaged seat, debris, worn seal |
| Chatters during operation | Dirty seat, unstable vacuum source |
Recommended Maintenance
To maintain reliable operation:
- Inspect the valve during routine service intervals.
- Keep the valve clean and free of debris.
- Test annually or according to your company's maintenance schedule.
- Replace the valve if opening pressure cannot be verified or corrected.
Safety Reminder
Never bypass, disable, or operate a vacuum system with a defective vacuum relief valve. This valve is a critical safety device designed to protect both equipment and personnel from dangerous over-vacuum conditions. Regular testing and inspection help ensure safe, reliable operation of your vacuum system while extending the life of your tank and associated equipment.